WAVE commercial heat pumps( industrial heat pumps) are new generation heat pump water heaters: instant-heating type units, cold water (like 10℃) goes into the unit, then comes out with terminal temperatures (like 55℃). So in a commercial water heating project we only need a storage water tank. Traditional products are circulation-heating type: which can only raise several degrees (like 3-5℃) one time, so they need both storage tanks and circulation tanks.
We supply 4 models with input powers from 1.0Kw to 12.5Kw. Users can compose a very big water heating project by modular installation. To see application examples, click here.
Models: WES-10 /WES-28 /WES-60 /WES-125
ADVANTAGES
+
Adopt leading
heat pump technology of USA, COP reaches 3~6.
+
Distinctive S.C.L heat
exchange equipment, guarantee high heating efficiency and
stability.
+
Humanized control system, 11-layer
safety guard, water-electricity separated entirely. No worry
about leakage, poisoning or burning. Using safely and reliably.
+
System 24-hour on/off setting.
+
Do not need special machine room
for units. Convenient installation. The heat pump system can be
combined with the former water heating system.
+
Service life >12 years.
+
Advanced
defrosting, pressure self-poise function. Able to run in low and
high ambient air temperature.
+
As energy
efficient and environment friendly equipments, heat pumps are
encouraged in many countries. WAVE products have no
special limits and can run without anybody on guard.
SPECIFICATIONS
In Ambient Air Temp of
20°C
Model
WES-10
WES-28
WES-60
WES-125
heating
capacity
Kw
4.5
12.5
26.7
55.6
rate power
Kw
1
2.8
6
12.5
hot water
supply △t=40
L/hr
100
270
570
1200
hot water
supply △t=35
L/hr
110
310
660
1370
rate
current
A
4.8
12.6
8.8
16.7
max input
power
Kw
1.38
3.8
7.2
17
max input
current
A
6.2
15.2
11
24.5
power
system
220V,50Hz
220V,50Hz
380V,50Hz
380V,50Hz
system
control
on-off
automatically, multi-protection and trouble
alarm
water-out
temp
℃
57℃
default, 40℃~70℃ adjustable
evaporator form
inner thread copper tube+fin wing
with copper foil
net weight
Kg
42
140
260
380
noise
dB(A)
≤51
≤60
≤60
≤60
net size
mm
850x305x610
910x337x1400
670x1250x820
1380x690x1520
packing size
mm
980x390x680
1130x405x1380
1280x700x930
1485x745x1705
max pressure of water system
Mpa
1.2
1.2
1.2
1.2
*Data based on: Ambient air temp 20℃
DB/19℃
WB, water-in temp 15℃, water-out temp 55℃.
*If data changes due to product
improvement, please take the objects as reference.
In Ambient Air Temp of 7°C
Model
WES-10
WES-28
WES-60
WES-125
heating capacity
Kw
2.8
8
17
34
rate power
Kw
0.95
2.6
5.6
11.2
hot water supply △t=46
L/hr
52
150
320
640
hot water supply △t=40
L/hr
60
172
370
731
hot water supply △t=35
L/hr
70
200
420
840
rate current
A
4.5
12.6
8.1
16
max input power
Kw
1.38
3.8
7.2
17
max input current
A
6.2
15.2
11
24.5
power system
220V,50Hz
220V,50Hz
380V,50Hz
380V,50Hz
running control
on-off automatically, multi-protection and trouble alarm
water-out temp
℃
57℃
default, 40℃~70℃ adjustable
evaporator form
inner thread copper tube+fin wing with copper foil
net weight
Kg
42
140
260
380
noise
dB(A)
≤51
≤60
≤60
≤60
net size
mm
850x305x610
910x337x1400
670x1250x820
1380x690x1520
packing size
mm
980x390x680
1130x405x1380
1280x700x930
1485x745x1705
max pressure of water system
Mpa
1.2
1.2
1.2
1.2
*Data based on: Ambient air temp 7℃
DB/6℃
WB, water-in temp 9℃, water-out temp 55℃.
*If data changes due to product
improvement, please take the objects as reference.
In Ambient Air Temp of 0°C
Model
WES-10
WES-28
WES-60
WES-125
heating capacity
Kw
2.4
7.2
13.6
27.2
rate power
Kw
0.92
2.5
5.4
10.8
hot water supply △t=46
L/hr
44
128
272
544
hot water supply △t=40
L/hr
51
146
315
621
rate current
A
4.4
11.6
8.0
15.5
max input power
Kw
1.38
3.8
7.2
17
max input current
A
6.2
15.2
11
24.5
power system
220V,50Hz
220V,50Hz
380V,50Hz
380V,50Hz
running control
on-off
automatically, multi-protection and trouble
alarm
water-out temp
℃
57℃ default,
40℃~70℃ adjustable
evaporator form
inner thread copper tube+fin wing with copper
foil
net weight
Kg
42
140
260
380
noise
dB(A)
≤51
≤60
≤60
≤60
net size
mm
850x305x610
910x337x1400
670x1250x820
1380x690x1520
packing size
mm
980x390x680
1130x405x1380
1280x700x930
1485x745x1705
max pressure of water system
Mpa
1.2
1.2
1.2
1.2
*Data based on: Ambient air temp 0.2℃ DB/0.5℃
WB, water-in temp 9℃, water-out temp 55℃.
*If data changes due to product improvement,
please take the objects as reference.